h1288g interbus.pdf

(805 KB) Pobierz
Hardware and Engineering
Hardware and Engineering
DE4-NET-S
Interface-Module for INTERBUS
03/01 AWB823-1288-GB
1 st published 2001, edition 03/01
© Moeller GmbH, Bonn
Author: Andreas Ratsch
Editor: Michael Kämper
Translator: David Long, Moeller
All brand and product names are trademarks
or registered trademarks of the owner
concerned.
All rights reserved, including those of the
translation.
No part of this manual may be reproduced in
any form (printed, photocopy, microfilm or
any otherprocess) or processed, duplicated or
distributed by means of electronic systems
without written permission of Moeller GmbH,
Bonn.
Subject to alterations without notice.
457264322.001.png
Caution!
Dangerous Electrical Voltage!
Earth and short circuit.
Cover or enclose neighbouring units that
are live.
Follow the engineering instructions
(AWA) of the device concerned.
Only suitably qualified personnel may
work on this device/system.
Before installation and before touching
the device ensure that you are free of
electrostatic charge.
Emergency stop devices complying with
IEC/EN 60 204-1 must be effective in all
operating modes of the automation
devices. Unlatching the emergency-stop
devices must not cause uncontrolled
operation or restart.
Devices that are designed for mounting
in housings or control cabinets must only
be operated and controlled after they
have been installed with the housing
closed. Desktop or portable units must
only be operated and controlled in
enclosed housings.
Measures should be taken to ensure the
proper restart of programs interrupted
after a voltage dip or failure. This should
not cause dangerous operating states
even for a short time. If necessary,
emergency-stop devices should be
implemented.
According to their degree of protection
frequency inverters may feature during
operation live, bright metal, or possibly
moving, rotating parts or hot surfaces.
The impermissible removal of the
necessary covers, improper installation
or incorrect operation of motor or
frequency inverter may cause the failure
of the device and may lead to serious
injury or damage.
The relevant national regulations apply to
all work carried on live frequency
inverters.
Connecting cables and signal lines
should be installed so that inductive or
capacitive interference do not impair the
automation functions.
Install automation devices and related
operating elements in such a way that
they are well protected against
unintentional operation.
Suitable safety hardware and software
measures should be implemented for the
I/O interface so that a line or wire
breakage on the signal side does not
result in undefined states in the
automation devices.
Ensure a reliable electrical isolation of
the low voltage for the 24 volt supply.
Only use power supply units complying
with IEC 60 364-4-41 or HD 384.4.41 S2.
The electrical installation must be carried
out in accordance with the relevant
regulations (e. g. with regard to cable
cross sections, fuses, PE).
Deviations of the mains voltage from the
rated value must not exceed the
tolerance limits given in the
specifications, otherwise this may cause
malfunction and dangerous operation.
I
Before commencing the installation
Disconnect the power supply of the
device.
Ensure that devices cannot be
accidentally restarted.
Verify isolation from the supply.
457264322.002.png
All work relating to transport, installation,
commissioning and maintenance must
only be carried out by qualified
personnel. (IEC 60 364 and HD 384 and
national work safety regulations).
Installations fitted with frequency
inverters must be provided with
additional monitoring and protective
devices in accordance with the relevant
safety regulations etc. Modifications to
the frequency inverters using the
operating software are permitted.
In order to reduce hazards to persons or
equipment, the user must include in the
machine design measures that restrict
the consequences of a malfunction or
failure of the drive (increased motor
speed or sudden standstill of motor).
These measures include:
– Other independent devices for
monitoring safety-related variables
(speed, travel, end positions etc.)
– Electrical or non-electrical system
related measures (interlocks or
mechanical interlocks).
– Live parts or cable connections of the
frequency inverter must not be
touched after it has been
disconnected from the power supply
due to the charge in capacitors.
Appropriate warning signs must be
provided.
All shrouds and doors must be kept
closed during operation.
II
Contents
About This Manual
6
Abbreviations and symbols
6
1 About This Interface
8
INTERBUS system
8
INTERBUS interface
9
Features of the DE4-NET-S
10
Design of the DE4-NET-S
11
Manufacturer’s declaration
12
Intended use
12
Persons responsible for safety
13
Disposal
14
2 Engineering
16
INTERBUS input
16
INTERBUS output
17
Supply voltage
17
External supply voltage
18
Potential isolation
18
Preventing faults
19
Communication data
21
Execution time in the frequency inverter
22
3 Installation
24
Items supplied
24
Fitting to the frequency inverter
24
Wiring with the host computer
26
1
Contents
4 Configuration/Parameter Definition
28
Communication channels
28
Process data
29
DRIVECOM parameters
31
DRIVECOM parameter table
33
DRIVECOM device control
35
DRIVECOM control word (6040 hex)
39
DRIVECOM status word (6041 hex)
43
Monitoring
46
Process data configuration
47
RPM/speed channel
51
PCP communication services
59
5 Operation/Diagnostics
66
Commissioning
66
Enable frequency inverter
69
Diagnostics
71
Appendix
74
Technical Data
74
Contact address
75
Standards and specifications
76
Dimensions
76
Index
78
2