TCC-Link Configuration
For further details, please contact Toshiba Customer Service on 0870 8430333
Product Bulletin 503-0507
TCC-Link indoor unit configuration
Description
TCC-Link indoor units (split systems or VRF) can be
configured from the standard controller (RBC-AMT21E or
RBC-AMT31E). If necessary, the standard controller may be
temporarily connected during the configuration process.
Configurations are dependant on the indoor unit style.
Any other type of controller used will maintain configuration
changes – power failure will not change any settings.
Ö
Connect a standard controller to a control group
Ö
Enter configuration mode by pressing TEST (spanner
icon) + SET + CL for 4 seconds
Ö
The group master indoor unit will be the first available to
configure – to change, press UNIT button until the
appropriate address is displayed.
Ö
Scroll through the configuration items by using the
temperature
ST
buttons.
Ö
Modify the configuration value by using the timer
ST
buttons
Ö
Press SET to confirm any changes made.
Ö
Select another item and/or indoor unit by repeating
procedure
Ö
Press TEST (spanner icon) to exit configuration mode.
Ö
System will take approximately 1 minute to update the
database.
Method
Item
Description
Location
Value
Default
01
Dirty filter alarm
Master
0000 = off
0001 = 150 h
0002 = 250 h
0003 = 500 h
0004 = 1000 h
0005 = external switch (CN70 n/o)
0004
02
Dirty filter – halves time set in item 01 Master
0000 = normal
0001 = dirty environment
0000
03
Central control address. Only
applicable when central control is
applied.
Master
0099 = unset
0001 to 0016 = zone 1
0017 to 0032 = zone 2
0033 to 0048 = zone 3
0049 to 0064 = zone 4
0099
04
Priority indoor unit – SMMS only.
Prioritised indoor unit chooses
operating mode of system.
DIP switch 11 bits 1 and 2 must be
set ON (master outdoor unit)
Individual
0000 = non-priority indoor unit
0001 = prioritised indoor unit
0000
05
Indoor fan control when indoor unit is
in satisfied in heat mode and
satisfied and the compressor is either
ON/OFF
Individual
0000 = low for 1 min. then low-low/low-low
0001 = low speed/low low speed
0002 = low-low speed
0003 = stopped/fan at low-low speed
0004 = Low fan when compressor is OFF
0005 = Low fan when compressor is OFF
0006 = Low fan when compressor is OFF
0007 = Low fan when compressor is OFF
0008 = Fan off when compressor is OFF
0009 = Fan off when compressor is OFF
0010 = Fan off when compressor is OFF
0011 = Fan off when compressor is OFF
0001
06
Stratification control. Increases
effective set point of indoor unit when
heating. Not used when controller’s
temperature sensor is used (DN 32)
Individual
0000 = no increase
0001 to 0010 = increased by 1 to 10 K
0003
08
Drain pump operation with no cooling
demand
Individual
0000 = pump stops
0001 = pump operates
0000
09
Drain pump operation in FAN ONLY
mode
Individual
0000 = pump stops
0001 = pump operates
0000
Bulletin 503-0507 1 of 4
2 November 2005
TCC-Link Configuration
For further details, please contact Toshiba Customer Service on 0870 8430333
Item
Description
Location
Value
Default
0A
Remote controller’s temperature
sensor
0000 =
0001 =
0000
0b
Demand input function switch
0000 =
0001 =
0000
0C
Preheat indication
Master
0000 = available
0001 = unavailable
0000
0d
Auto mode - availability
Master
0000 = available
0001 = unavailable
0000 except
SMMS
0E
All indoor units operate in the same
mode as master. Must be used with
SHRM 2 series when multiple indoor
unit are served by a single FS unit
All in group
0000 = individual mode selection
0001 = group mode selection
0000
0F
Heat mode - availability
Master
0000 = available
0001 = unavailable
0000
10
Indoor unit style. Configures fan
motor style, louver operation and fan
speed availability.
Individual
0000: 1 way cassette (S models)
0001: 4 way cassette
0002: 2 way cassette
0003: 1 way cassette (Y models)
0004: duct (standard)
0006: duct (high static)
0007: ceiling
0008: hi wall
0010: console
0011: concealed floor
0013: tall cabinet
Must be set up when replacing indoor
PCB.
11
Indoor unit capacity.
Individual
0000 = invalid (L09 fault code)
0001 = 0.8 HP
0003 = 1 HP
0005 = 1.25 HP
0007 = 1.7 HP
0009 = 2 HP
0011 = 2.5 HP
0012 = 3 HP
0013 = 3.2 HP
0015 = 4 HP
0017 = 5 HP
0018 = 6 HP
0021 = 8 HP
0023 = 10 HP
Configures airflow and demand (VRF
models).
Must be set up when replacing indoor
PCB.
12
System address (first part of indoor
address).
Individual
0001 to 0028
0099 (unset)
13
Indoor unit address (second part of
indoor address)
Individual
0001 to 0064
0099 (unset)
14
Group arrangement
Individual
0000 = group of 1 indoor unit
0001 = group master (multiple indoor units)
0002 = group slave (multiple indoor units)
0099 (unset)
15
Compensates for missing
temperature sensor (split system
only) – other settings result in fault
code.
Individual
0022 (split systems)
0021 (one way cassette – VRF range)
0022
16
Indoor fan speeds available
Master
0001 = A
0002 = L
0003 = A + L
0004 = M
0006 = A + L + M
0008 = H
0010 = A + L + H
0012 = M + H
0015 = A + L + M + H
0015 except
high static
duct (0008)
17
Cooling temperature set point shift
(COOL mode)
Master
0000 = no shift
0001 to 0010 = shifted by 1 to 10 K
range of adjustment is –10 to +10
0000
19
Louver control - availability
Master
0000 = disabled
0001 = swing on or off
0004 = swing on or off + settable
Model
dependant
1b
Cool/heat minimum demand time
Individual
0000 = 5 minutes
0001 = 4 minutes
0000
1C
Indoor temperature sensor value
adjustment
Individual
0000 = no shift
0001 to 0010 = shifted by 1 to 10 K
range of adjustment is –10 to +10
0000
1E
Dead band in AUTO mode
Individual
0000 = no dead band
0001 to 0010 = dead band 1 to 10 K
0003
Bulletin 503-0507 2 of 4
2 November 2005
TCC-Link Configuration
For further details, please contact Toshiba Customer Service on 0870 8430333
Item
Description
Location
Value
Default
1F
Maximum temp. setting (COOL)
Master
0030 = 30°C (maximum value)
0030
20
Minimum temp. setting (COOL)
Master
0017 = 17°C (minimum value)
0018
21
Maximum temp. setting (HEAT)
Master
0030 = 30°C (maximum value)
0026
22
Minimum temp. setting (HEAT)
Master
0017 = 17°C (minimum value)
0016
23
Maximum temp. setting (DRY)
Master
0030 = 30°C (maximum value)
0030
24
Minimum temp. setting (DRY)
Master
0017 = 17°C (minimum value)
0018
25
Maximum temp. setting (AUTO)
Master
0030 = 30°C (maximum value)
0027
26
Minimum temp. setting (AUTO)
Master
0017 = 17°C (minimum value)
0017
28
Auto restart enable
Master
0000 = disabled
0001 - enabled
0000
29
Humidifier control based on coil
temperature – not used.
0000 = enabled
0001 = disabled
0000
2A
Configuration of CN70
0000 = Filter pressure switch
0001 = Alarm input
0002 = Alarm input (fault code L30)
0002
2b
Compressor control
Individual
0000 = compressor under temp. control
0001 = compressor on
0000
2d
Modes available – binary addition
Master
0015 = all modes available
1 = fan; 2 = cool; 4 = dry and 8 = heat
0015
2E
External on/off control by
making/breaking terminals 1 and 2 of
CN61 (yellow plug on indoor PCB.
Hotel card key applications.
Cutting jumper 01 on the master
indoor PCB allows a continuous
contact switch – otherwise it requires
pulsed switching. Central control
padlock is displayed when held off.
Individual
0000 = group starts when made and stops
when broken - changes may be made
through the day
0001 = enables when made, disabled when
broken.
0000
30
Motorised filter
Master
0000 = disabled
0001 = enabled
Dependant on
indoor unit
31
External fan control – through
controller and CN32 (indoor PCB)
Master
0000 = disabled
0001 = enabled
0000
32
Remote controller’s temperature
sensor
Master
0000 = disabled – uses return air
0001 = enabled – all other sensors
disabled. Icon displayed on controller.
0000
33
Unit of temperature
Master
0000 = Celsius
0001 = Fahrenheit
0000
40
Drain pump operation in cooling
mode.
Individual
0000 = No pump
0001 = Pump on
0002 = No pump
0003 = Pump off
Dependant on
indoor unit
45
4-way cassette – anti smudging
effect – via louver position
Individual
0000 = enabled
0001 = disabled
0000
5d
Air flow configuration for high wall;
standard duct; ceiling and 4 way
cassette indoor units
Individual
0000 = standard
0003 = high (duct)
0004 = low (except duct)
0006 = low (duct) and high (others)
0000
60
Elapsed timer lock (RBC-AMT21E
only). This is disabled when
connecting an external timer.
Master
0000 = unlocked
0001 = locked
0000
62
4-way cassette – anti smudging
effect – via fan speed (Coanda
effect)
Individual
0001
69
Louver restriction when cooling
Individual
0000 = restricted to horizontal positions
0001 = full range of movement
0000
88
Air blocking kit used on 4 way
cassette
0000 = not blocked
0065 = blocked
0000
8b
Heating output reduction (hi wall, split
systems only)
Individual
0000 = disabled
0001 = enabled
0000
8C
Forced defrost. Run group in HEAT
mode after setting – defrost is
conducted automatically. Value is
automatically set back to 0000.
Individual
0000 = disabled
0001 = enabled
0000
91
Certification settings (reduced)
Individual
0000 = standard
0001 = test
0002 = low capacity
0000
92
Configuration of CN70 input
0000 = stop with L30 code
0001 = continued operation with L30 code
0000
A0
Fan and pump operation during oil
retrieval – VRF cassettes only.
Individual
0000 = fan off, pump on
0003 = fan on, pump on
0003
Bulletin 503-0507 3 of 4
2 November 2005
Configuration menu examples
Standard Remote no power applied.
No lines shown on the display.
Standard Remote with power applied – controls
are configuring.
Lines only displayed.
Standard display after configuration has finished.
To access configuration mode, press
+ SET + CL for 4 seconds.
This is the initial configuration display.
The menu number is displayed at the top right,
in this case 00, in some cases 10 is displayed.
Use the temp up/down buttons to select the
menu to be changed.
The contents of the menu, or sub-menu, is
displayed top left, in this case 0020.
Page 42 of 52
Plik z chomika:
bogumilka
Inne pliki z tego folderu:
Termostato_NO_programable.pdf
(189 KB)
CQ-RDP930(1).pdf
(2492 KB)
990-2316-PL(1).pdf
(1017 KB)
59f1b7b3735a2cf5d859d214d8c3bc9b(1).pdf
(8289 KB)
44_17.LEANDmanual(1).pdf
(138 KB)
Inne foldery tego chomika:
Pliki dostępne do 01.06.2025
3D xxx pass xxxxx
Camera
Coben Harlan - Bez pozegnania [Zlotopolsky]
Coben Harlan - Jeden falszywy ruch
Zgłoś jeśli
naruszono regulamin